Spec:
Item Type: Particle Dust Transmitter
Material: ABS
Model: RS PM N01 2
DC Power Supply: DC 10-30V
Output: 485 Communication (for Modbus Protocol)
Baud Rate: 2400, 4800 (Default), 9600
Data Bit Length: 8 Bits
Parity Check Mode: None
Stop Bit Length: 1 Bit
Default for Modbus Communication Address: 1
Support Function Code: 03
Parameter Setting: Configuration through 485 interface using the supplied configuration software
Maximum Power Consumption:
Current Output: 1.2W
Voltage Output: 1.2W
RS485 Output: 0.4W
Current Output: 4-20mA
Voltage Output: 0-5V, 0-10V
RS485 Output: RS485 (for Modbus Protocol)
Load Capacity.
Voltage Output: Output Resistance ≤ 250Ω
Current Output: ≤600Ω
Measurement Range:
PM2.5: 0-1000μg/m³
PM10: 0-1000μg/m³
Resolution: 1μg/m³
Preheating Time: ≤2MIN
Response Speed: ≤90S
Accuracy: Particle Counting Efficiency: 50% at 0.3um, 98% at ≥0.5um
PM2.5 Accuracy: ±3%FS (at 100ug/m³, 25℃, 50%RH)
Protection Grade: IP65
Working Environment: -20℃-+60℃,0%RH-80%RH
PackageList:
1 xParticle DustTransmitter
2 x Screw
2 x Expansion Tube
Note:
Common troubleshooting:
1. PLC cannot collect data
A: Please check the output type of the device; whether the device is turned on.
2. The collected differs greatly from the actual
A: Please check the equipment range and data conversion relationship.
3. Transmitter output jumps
A: The distance between transmitter and collector is too far, resulting in disorder.
4. How to quickly determine the problem
A: Temporarily without post acquisition equipment, multimeter measurement of transmitter output.