Feature

●Generator Controller is an outstanding compact control module that provides a comprehensive range of features for single-set applications.
●Generator Set Start & Protect: Used to start and protect a single generator set, realize the manual and remote start and stop of the generator set, data measurement, alarm indication, shutdown protection, etc.
●Light touch button operation to achieve precise measurement of various parameters, all configuration parameters can be adjusted from the front panel of the controller
●Reliable Operation Easy Installation: generator set controller has the advantages of simple operation, reliable operation, compact structure, and convenient installation
●embedded installation method, small size and easy installation


Description

The main technical parameters:
DC power supply: 8-35V
Power generation input: AC15-300V(+20%) 50 or 60Hz programmable
Overspeed threshold: 114% of rated frequency
Starter separation: generator voltage 15VAC and frequency 15Hz
Charging failure voltage: less than 3V
Idle time: the factory default is 10 seconds
5 output ports: 1A current, DC power supply B+ relay output
4 switch input ports: connect to B- effective
Hour meter: maximum display time 99999.9 hours
Working temperature: -30-+70
Power consumption: standby (12V: 0.12W, 24V: 0.24W), normal operation (12V: 0.5W, 24V: 1W)
Appearance size: 84x72x35mm
Weight: 0.2Kg
7 TERMINALS FUNCTION
Terminal 1 (B-): Connected to plant battery negative.
Terminal 2 (B+): Connected to plant battery positive.
Terminal 3 (Fuel Output): Fuel Output (B+), Connected to fuel relay.
Terminal 4 (Start Output): Start Output (B+), Connected to start relay.
Terminal 5 (Pre-heat Output): Pre-heat Output (B+).
Terminal 6 (Aux. Shutdown Input): auxiliary shutdown alarm input, connect to B- active.
<;3V), annunciator on the panel illuminates. (indication only, not shutdown)
Terminal 8 (Low Oil Pressure Input): Low Oil Pressure Input port, connect Bactive.
Terminal 9 (High Engine Temp input): High water/cylinder temperature input port, connect to B- active.
Terminal 10 (L), 11(N): Connect to AC voltage signal for detecting crank disconnect and over speed protection.
Terminal 12 (Config. Output): Config. Output (B+), can be set as idle/high speed output or common alarm via dial switch of the controller.
Terminal 13 (Stop Output): Energize to stop (ETS) (B+).