Burndy type YGHP-C irreversible compression ground tap figure 6 can be used as a ground rod tap connector for both continuous run and tapping applications. An open groove allows ground rod to be connected to a continuous run or tap. The second groove is for a tap only. Prefilled with Penetrox E and strip sealed. UL467 Listed for direct burial in earth or concrete. UL listed. CSA certified. IEEE - 837. The tooling recommendation has been designed to ensure a reliable, depend- able connection every time. The die index number is embossed on conductor after completion of crimp. Faciliates speedy inspection of installed connectors to insure consistently reliable and dependable connections. Prefilled with Penetrox E and individually sealed in clear polyethylene sheet. Ensures the electrical integrity of the finished connection by inhibiting moisture and contaminates from entering the contact area. Maintains long-term high-conductivity. UL467 Listed. May be used in direct burial or concrete embedded grounding applications. Provides quality assurance to recog- nized industry NEC standards from an independent party. "Third Hand" constrains conductors while installer completes crimp. Included with each connector. Simplifies installation, reducing installed cost.