Feature

●1. Test leakage initiating current of various kinds of leakage protector, Range : 15mA~500mA
●2. Test leakage operating time, Range: 0ms~999ms
●3. Line Voltage: below 250V
●4.Gear Current Accuracy ±(5%+2dgt)
●5. High accuracy, small size, light weight, delicate appearance and easy to carry, the meter is an ideal tool for on-site or indoor detection of various leakage protectors.


Description

Batteries are not included!!!

Overview:
It can test leakage initiating current, residual non-operating current and leakage operating time of various kinds of leakage protector (Range:0ms~999ms), and with manual and automatic two test modes.
The operation is simple, with backlight function, and the measurement result is directly displayed on a large screen,which is clearly visible even in a dark place. current test have 10 grades were 15, 30, 50, 75, 100, 150, 200, 250, 300, 500mA respectively.
High accuracy, small size, light weight, delicate appearance and easy to carry, the meter is an ideal tool for on-site or indoor detection of various leakage protectors.

Specification:
*Power Supply: DC 6V LR03 1.5VX4PCS
*Rated Voltage: AC 220V
*LCD Size: 44mm×27mm
*Leakage Current Gear: 15, 30, 50, 75, 100, 150, 200, 250, 300, 500mA
* Gear Current Accuracy: ±(5%+2dgt)
* Test Leakage Operating Time Range: 0~999ms
* Leakage OperatingTime Display : Accuracy :±2ms
*Power Consumption: Φ40mA
*Working Temperature: -10oC~40oC, below 80%rh
*Storage Temperature: 10oC~60oC, below 70%rh
* Test Mode :Manual or automatic
*Test Wire Length: 1.8M
* Failure Information Indication:LCD display “fault” failure information indication, it is possible that the rated initiating current grade of tested is too small or the leakage protector is faulty
* Line Voltage Test:Below AC 250V
* Battery Voltage Alarm:When the battery voltage lower than 4.8V, low battery voltage symbol display, and remind to replace the battery. The measurement value is also accurate at this time
*Insulator Strength: AC 2KV/rms (between the core and out shell)
*Suitable for safety regulations :IEC1010-1, IEC1010-2-032, Pollution degree 2, CAT III (600V) IEC61326(EMC standard)
*Clamp Weight: 350 g
* Clamp Size :170mm×75mm×30mm